EtherCAT
Product search
Product Catalog

US-EC-D00016N
Supports standard EtherCAT communication protocol
16 channel output, NPN
16 channel output, NPN
| Digital output parameter | ||
| Model number | US-EC-D00016N | |
| Number of channels | 16 | |
| Signal type | NPN | |
| "ON" signal voltage | DC 0V (±3%) | |
| "OFF" signal voltage | DC 24V (±25%) | |
| Channel light | Green | |
| Reverse circuit protection | Yes | |
| Load type | Resistive load, inductive load | |
| Isolation mode | Optical isolation from the field layer | |
| Single channel rated current | Max:500 mA(from UA) | |
| Port protection | Overcurrent protection | |
| Output interface | M12-A,5Pin,Hole end | |
| Total output current | Max:8 A(from UA) | |
| Communication parameter | ||
| Communication protocol | EtherCAT | |
| Transmission rate | 10/100Mbps full duplex | |
| Communication distance | ≤100 m (station distance) | |
| Station type | Remote I/O station | |
| Occupied work station | 1 station | |
| Address setting | EtherCAT specification | |
| Topological structure | Bus topology | |
| Isolation mode | Electrical isolation from field floor | |
| Transmission medium | 2×M12,4Pin,D-code | |
| Alarm function | Diagnostic alarm, process alarm | |
| Power supply parameter | ||
| Connection mode | 2×M12,5Pin,L-code | |
| US Rated power voltage | 24V DC (18V DC ~ 36V DC) | |
| US Maximum current of the power supply | Maximum input 16A, maximum output 16A (I/O port external disabled + 24V power disabled) | |
| US Reverse polarity protection | Support | |
| UA Rated power voltage | 24V DC (18V DC ~ 36V DC) | |
| UA Maximum current of the power supply | Maximum input 16A, maximum output 16A (DO disabled) | |
| UA Reverse polarity protection | Support | |
| Electrical isolation between GNDS and GNDA | Yes | |
| Basic parameter | ||
| Class of protection | IP67 | |
| Overall dimension | 225×62×35.1mm | |
| Operating temperature | -25 ~ 70℃ | |
| Storage temperature | -40 ~ 85°C | |
| Relative humidity | 95% (non-condensing) | |
| Authentication | CE | |
| Altitude/pressure | 0~2000 m (80kPa) | |
| Pollution level | Level 2 | |
| Immunity to interference | Power cable 2kV (IEC 61000-4-4) | |
| Overvoltage class | II | |
| LED status | ||
| Network indicator LINK | On: The network connection is successful | |
| Off: The network connection fails | ||
| Network indicator ACT | Blinking: Data is being transmitted | |
| Off: No data is being transmitted | ||
| US System power indicator | On: The power supply is normal | |
| Off: The product is powered off or the power supply is abnormal | ||
| UA Load power indicator | On: The power supply is normal | |
| Off: The product is powered off or the power supply is abnormal | ||
| RUN | On: The system is running properly | |
| Blinking: The device is in the Pre-OP or Safe-OP state | ||
| Off: The device is in Init or powered off state | ||
| ERR | On: The system is not running properly | |
| Blinking: The device is offline or the configuration of the slave station is incorrect | ||
| Off: The system is running properly or is powered off | ||
| Channel light | On: The signal of the corresponding channel is valid | |
| Off: The signal of the corresponding channel is invalid | ||
English
Chinese
